How DNP3 works

A working introduction to the protocol this library implements, for someone who has to read a frame or decide what an outstation should do, rather than a restatement of the standard. Where this page and IEEE 1815 disagree, the standard is right.

What it is

DNP3 moves telemetry and control between a control center and field equipment. It was designed for electric utilities communicating over slow, noisy serial links, and nearly every decision in it follows from that: checksums on every few octets, a transport layer whose whole job is to cut a message into pieces that fit a frame, and a data model that lets a master ask "what changed" rather than re-read everything.

It was later carried over TCP, on the port IANA assigns it, 20000, without changing any of that framing. A DNP3 conversation over a modern network is still shaped by the radio link it was designed for.

Standardized as IEEE 1815.

Two roles

A master asks; an outstation answers. The master polls on a schedule and issues controls. The outstation holds the data for one device and replies.

The asymmetry is worth holding on to, because it is not a peer protocol: an outstation never initiates a request. It can push an unsolicited response when something changes, but only if the master has enabled them, and that is a report rather than a question.

This library implements the outstation side.

Three layers

Layer What it carries Bound
Data link One frame: addresses and a checksummed payload 292 octets
Transport One octet, cutting a fragment into frames 249 octets of payload per frame
Application One fragment: a function code and objects 2048 octets, by convention

A frame starts with the two octets 0x05 0x64, then a length, a control octet, a 16-bit destination and a 16-bit source address. A CRC-16/DNP covers that header, and another covers every 16 octets of user data. A 292-octet frame carries 32 octets of checksum.

That density is the serial heritage. It means a corrupted frame is usually rejected within a few octets of the corruption rather than at the end.

The control octet carries the direction, whether this frame is primary (it starts a link transaction) or secondary (it answers one), and a link function: reset the link, request its status, or carry user data with or without confirmation.

Code Primary, which starts a transaction Secondary, which answers one
0 RESET_LINK_STATES ACK
1 NACK
2 TEST_LINK_STATES
3 CONFIRMED_USER_DATA
4 UNCONFIRMED_USER_DATA
9 REQUEST_LINK_STATUS
11 LINK_STATUS
15 NOT_SUPPORTED

The same four bits mean different things in the two directions, so a decoder reads the primary bit before it reads the function. This library's master sends UNCONFIRMED_USER_DATA and leaves delivery to TCP. Its outstation accepts either form, but confirmed user data only once the master has reset the link: before that there is no frame count to check it against, and the frame is dropped without a reply.

Addresses are 16-bit and little endian. Anything at or above 0xFFF0 is reserved, leaving 0 through 0xFFEF for stations, and three of the reserved values are broadcasts: 0xFFFD wants no confirmation, 0xFFFE requires one, and 0xFFFF leaves it optional. A frame that arrives on one of those is what sets the broadcast indication below.

The link address is not authorization

Source and destination are 16-bit integers chosen by whoever is sending. They identify a conversation; they do not establish who is on the other end. That distinction is the reason this library's TLS listener requires an explicit allow-list (D8).

Transport

A single octet: FIN, FIR, and a six-bit sequence number. Its entire job is to split an application fragment across as many link frames as it needs and reassemble it on the other side.

FIR and FIN swap places

The transport octet is FIN 0x80, FIR 0x40. The application control octet is FIR 0x80, FIN 0x40. The two layers assign them to opposite bits.

This is the kind of detail an implementation can get wrong consistently on both sides and never notice, which is why this library pins both to literal octets rather than to round trips.

Application

A fragment begins with a control octet carrying FIR, FIN, CON (a confirmation is requested) and UNS (this is unsolicited), plus a four-bit sequence. Then a function code. Then, on a response, the two internal indication octets. Then object headers and their data.

A frame, octet by octet

An integrity poll, master 1 to outstation 10. Twenty-seven octets, one data block:

05 64 14 C4 0A 00 01 00 8F ED   header, and its checksum
C1                              transport: FIR, FIN, sequence 1
C1 01                           application: FIR, FIN, sequence 1; READ
3C 02 06                        group 60 variation 2, all objects: class 1
3C 03 06                        class 2
3C 04 06                        class 3
3C 01 06                        class 0
62 01                           checksum over the fifteen octets above

The header is the fixed part:

Octets Field
05 64 Start what to search a capture for
14 Length 20: the control octet, four address octets, fifteen of user data
C4 Control from the master, primary, UNCONFIRMED_USER_DATA
0A 00 Destination 10
01 00 Source 1
8F ED Checksum over the eight octets above, low octet first

The length counts neither the start octets, nor itself, nor any checksum, which is how a 27-octet frame comes to declare 20. frame_size() in Protocol layers does the same arithmetic the other way round.

Four object headers, three octets each, ask for the four classes. The event classes come first and class 0 last, so that a change held in a buffer is never applied over a newer static value. That is an integrity poll, and the rest of this page is mostly an explanation of those twelve octets.

Internal indications

Two octets on every response. DNP3 has no separate status channel, so this is how a master learns anything about the outstation that it did not specifically ask about.

The first octet is the state of the device, true regardless of the request:

Bit Meaning
0x01 the request arrived as a broadcast
0x02 0x04 0x08 class 1, 2 or 3 events are waiting
0x10 the clock needs setting
0x20 a point is in local control
0x40 device trouble
0x80 the device restarted and the master has not cleared it

The second octet is what went wrong with this request:

Bit Meaning
0x01 function not supported
0x02 object unknown
0x04 parameter error, including a fragment that did not parse
0x08 events were lost to a full buffer
0x10 already executing
0x20 configuration corrupt

The restart bit is the one a master clears by writing to it, which is why an otherwise read-only outstation still honors one write.

The data model

Every value is identified by a group and a variation, and addressed by a qualifier.

Group is what kind of point it is.

Group Contents
1, 2 Binary input, static and event
12 Control relay output block
20, 22 Counter, static and event
30, 32 Analog input, static and event
40, 41 Analog output status, and the output itself
50, 51, 52 Time
60 Class objects, which is how a master asks for "everything"
80 Internal indications, addressable as data
120 Secure authentication

Variation is how the value is encoded: 32-bit or 16-bit, integer or float, with or without a quality flag, with or without a timestamp. Group 30 variation 1 is a 32-bit analog input with flags; variation 5 is the same measurement as a single-precision float.

A master and an outstation must agree on variations, and that agreement is a document rather than a negotiation. This is what a device profile is for.

Qualifier says how the objects that follow are addressed. The two shapes that matter:

  • A range: a start and a stop index, for contiguous static data. "Indices 0 through 4" costs four octets regardless of how many points that is.
  • A count with an index prefix on each object, for events. Events are whichever points happened to change, so they are not a range, the same index can appear twice, and the points between two events need not have moved.
Qualifier What follows it Where it is used
0x00 an 8-bit start and stop index contiguous static data
0x01 a 16-bit start and stop index the same, past index 255
0x06 nothing at all every object in the group; what a class read sends
0x07 an 8-bit count a count of objects with no indices
0x08 a 16-bit count the same, where the count runs past 255
0x17 an 8-bit count, then an 8-bit index on each object events, and controls
0x28 a 16-bit count, then a 16-bit index on each object the same, past index 255

The octet is two fields: the low nibble says what the range looks like, and bits 4 to 6 say what prefixes each object, an index or a size, and how wide that prefix is. 0x06 is the one to memorize. It is what makes a class read three octets long, and therefore cheap enough to send every second.

Static data and events

This is the central idea, and the one most worth getting right.

Static data is what a point reads now. Event data is the record that it changed, carrying the value it held at the time, buffered until a master reads it.

A master that only ever read static data would see a sampled signal and miss everything between samples. A breaker that opened and reclosed between two polls did not happen, as far as static data is concerned.

Events are assigned to classes 1, 2 and 3. These are reporting priorities rather than data types: a class is a statement about how urgently something should be reported, and a master asking for class 1 wants everything assigned to class 1 whatever kind of point it came from. Class 0 is the static data.

An integrity poll reads classes 1, 2, 3 and 0 in one request: give me everything you have been holding, and then the current state of the world.

A deadband decides what counts as a change worth recording. Without one, a noisy analog input generates an event per reading and fills the buffer with noise nobody asked for. The deadband is the operator's statement of what movement matters.

Quality is not subject to the deadband

A point that goes comm-lost while holding the same number has not moved and has changed in the way that matters most. A deadband applied to quality would hide exactly the transitions someone is watching for.

Quality travels with each value, in a flags octet: online, restart, comm-lost, remote or local forced, over-range, reference error. A consumer has to be able to tell a fresh reading from a retained one, and arrival time cannot tell it.

Bit Binary input Analog input
0x01 online online
0x02 restart restart
0x04 comm-lost comm-lost
0x08 remote forced remote forced
0x10 local forced local forced
0x20 chatter filter over-range
0x40 reference error
0x80 the state itself

The low five bits mean the same thing in both, which is what lets a consumer decide whether a value can be trusted without knowing what kind of point it came from. Above them the two diverge, and on a binary input the top bit is the value itself, so a binary input whose flags octet is zero reads as an offline false rather than as a missing reading.

Function codes

Code Name
0 Confirm acknowledges a fragment; not a request
1 Read
2 Write
3, 4 Select, Operate the two halves of the control interlock
5 Direct Operate skips the interlock
6 Direct Operate, No Acknowledgment and asks for no reply
7 to 12 Freeze variants three of them ask for no reply
13, 14 Cold and Warm Restart
20, 21 Enable and Disable Unsolicited
23, 24 Delay Measurement, Record Current Time clock synchronization
129, 130 Response, Unsolicited Response

Select before operate

Controls have a safety interlock. SELECT arms a point, and the outstation echoes back what it understood. OPERATE then executes it only if the two match. A master that meant to open one breaker and misaddressed the request finds out before anything moves.

Direction Message
master -> outstation SELECT, group 12 variation 1, index 3, latch on
outstation -> master the block echoed back, carrying a status
master -> outstation OPERATE, the identical block
outstation -> master the block again, carrying the status of the operation

Both replies carry a status. The one on the select is what tells the master whether to go on to the operate.

DIRECT_OPERATE skips the interlock for cases where the round trip costs more than the mistake would.

The control block

A control is group 12 variation 1, eleven octets:

Octets Field
1 Control code what to do
1 Count how many times to do it
4 On-time milliseconds, for a pulse
4 Off-time milliseconds, for a pulse
1 Status zero in a request, the outcome in the reply

The control code is the octet to read carefully. Its low nibble is the operation: 1 pulse on, 2 pulse off, 3 latch on, 4 latch off. Its top two bits are the trip-close code, 1 close and 2 trip, which is how a single point operates equipment with a pair of coils. Between them sit two more bits. The queue bit is obsolete in IEEE 1815-2012: a master sets it to zero, and an outstation answers a control that sets it with NOT_SUPPORTED. The clear bit asks the outstation to cancel any pending or running control on that point first, and then to carry out the new one, if there is one. Support for it is optional.

A direct operate of latch-on against point 3. Thirty-three octets, and this one needs two data blocks:

05 64 18 C4 0A 00 01 00 3D 3A   header, and its checksum
C2                              transport: FIR, FIN, sequence 2
C2 05                           application: sequence 2; DIRECT_OPERATE
0C 01 17                        group 12 variation 1, count and 8-bit indices
01                              one control follows
03                              index 3
03                              control code: latch on, no trip-close
01                              count: once
00 00 00 00                     on-time, which a latch ignores
00 00                           off-time, first half
CE 33                           checksum: sixteen octets of user data end here
00 00                           off-time, continued
00                              status
FF FF                           checksum over the three octets above

A data block ends where it ends

The checksum lands in the middle of the off-time field, because a block is sixteen octets wherever that falls and knows nothing about the structure above it. A parser that reads fields as it strips checksums, rather than reassembling the user data first and parsing it afterwards, works on every short frame and then fails on this one.

The last checksum is FF FF because the three octets it covers are all zero and CRC-16/DNP complements its result. It is correct, and it looks exactly like a placeholder.

The functions that expect no reply

Five function codes carry a "no acknowledgment" meaning, and IEEE 1815-2012 Table 4-2 describes each as "same as function code N but outstation shall not send a response": 0x06, 0x08, 0x0A, 0x0C and 0x21.

The obligation is on the function code rather than on whether the outstation implements what was asked. An outstation that refuses one of these out loud is sending a fragment to a master that is not listening for it, and that is true even when the refusal is correct and even when the request did not parse.

What a session looks like

An outstation has restarted and a master reconnects:

Direction Message
master -> outstation read classes 1, 2, 3 and 0
outstation -> master the data, with the restart indication set
master -> outstation write zero to that indication bit
master -> outstation write the time, if the outstation asked for it
master -> outstation read classes 1, 2, 3 and 0 again

IEEE 1815-2012 5.1.1.1.2, rule 2, gives the order: clear the restart indication, then the optional steps with time synchronization among them, then the integrity poll. A master learns of the restart only from a response, so a poll comes first in practice and comes again once the indication is cleared.

Every step answers something the outstation said rather than something the master assumed. The restart bit is why the write happens, the clock bit is why the time follows, and an outstation that never asks for either is one the master leaves alone.

A master configured to use unsolicited reporting, once it has received the outstation's null unsolicited response, also asks the outstation to enable it (5.1.1.2, and the same rule). That is not a step every master takes, and an outstation built without unsolicited responses, which is this library's default, refuses the request.

After that the traffic settles into a repetition: event reads at whatever interval the deployment asks for, an integrity poll less often to repair anything the event path lost, and unsolicited responses in between where they are enabled. This library's master sends nothing on a schedule unless it is told to.

Security

DNP3 originally had none, which is why the protocol identifies but does not authenticate.

TLS is the usual answer over TCP. DNP3 Secure Authentication adds challenge-response at the application layer using group 120 objects, so that a critical request can be proven to come from who it claims to.

Neither is a substitute for deciding which peers may connect at all.

Conformance

Interoperability is graded in subset levels 1 through 4, level 1 being the minimum a device can implement and still be called DNP3. Higher levels add object groups, qualifiers and functions.

IEEE 1815.2 is the DER profile built on top, assigning specific indices to specific measurements for distributed energy resources. It is the target this library is built toward, and where it and Level 2 disagree, this library follows the profile and names the divergence.