Evaluating an outstation

py1815-master evaluate connects to an IEEE 1815.2 DER outstation, runs a list of checks against it, and prints a verdict for each. A check is a short procedure a controlling station would carry out: read a function's points, write its settings and read them back, enable and disable it, edit a curve. The same checks run against a device on a bench and against the simulated DER.

py1815-master evaluate --outstation lab=192.0.2.10:20000
lab at 192.0.2.10:20000, outstation 1024, 2026-10-09T16:39:39+00:00, read only
profile tables: IEEE Std 1815.2-2025

PROFILE-001  not applicable  Device Profile agrees with what is served
             no Device Profile document was given
MON-001      passed          Monitoring
             note: 24 of the meter's 24 points are served
ALARM-001    passed          Alarm reporting
             note: 22 of the 22 alarm points are served
OP-001       passed          Operating states
CONN-001     not run         Connect and disconnect
             it writes to the outstation, and the run was not allowed to
...

35 checks: 3 passed, 1 not applicable, 31 not run

The command needs the IEEE 1815.2 profile tables, which name the points and say how they are paired. See Serving a DER for how to get them.

A run with --allow-control changes the outstation

Without --allow-control the command only reads. With it, the checks write settings, enable and disable functions, write curves, open and close the connect switch, and stop and start the DER. Use it on a device on a bench, not on one in service. See What a run leaves behind.

Verdicts

Verdict Meaning
passed The outstation did everything the check requires
FAILED The outstation did something the check does not allow. The next line says what
not applicable The outstation does not serve what the check needs
not run The check writes and the run was read only, the check has the master break a protocol rule and the run was not allowed to, or the connection was lost earlier

A note line is something the check saw that does not decide the verdict: how many of a block's points are served, an alarm that was raised when read, a refusal with an unusual status.

The exit status is 0 when no check failed, 1 when one did, and 2 when the run could not be made: a setting that cannot be used, no tables, no connection, or no answer.

The checks

py1815-master evaluate --list prints them, each with its set and whether it reads, writes or deviates. --check NAME runs one check or one set, and may be repeated.

The der set carries out EPRI's Test Procedure for Validating DNP Application Note AN2018-001 in Distributed Energy Resources (report 3002016144). Each check is named for the identifier the report gives its procedure. The report was written for the application note that IEEE 1815.2 replaced; where the two differ, the checks follow the standard.

Check Writes What it requires
MON-001 no Every served point of the system meter is ONLINE and inside the range the tables give
ALARM-001 no Every served alarm is ONLINE
OP-001 no Every served operating state is ONLINE; started and stopped are not both set; and no more than one of BI18 to BI22 is set, with exactly one required when the outstation serves all five
CONN-001 yes The connect settings read back what was written, and the switch status follows a command to open and to close
SERV-001 yes The service settings read back, each permission follows its command, and a stop and a start are carried out and reported
SERV-001.2, SERV-001.3 yes A start, or a stop, is refused while its permission is withdrawn, and the DER stays as it was
CURVE-001 yes The referenced indicator is clear for a curve no function names and set once one does
CURVE-001.2 yes A curve beyond the last one stored cannot be selected
CURVE-002 yes A curve named by an enabled function cannot be edited, another curve can, and disabling the function releases it
CURVE-002.2 yes An enabled function can be pointed at another curve, which frees the one it left
CURVE-003 yes A function cannot be pointed at a curve of a type it does not follow, and such a curve cannot change type under it
CURVE-003.2 yes A function cannot be pointed at a curve with no type, or at one that does not exist
VRT-001 to PSIG-001 yes One check for each of the 21 functions, by the binary output that enables it. See below

Each function check first reads the input that says whether the outstation supports the function, and the report's title says which it found.

  • Supported. The function's inputs carry values and no ONLINE flag while it is disabled. Its settings are written and read back. It is enabled, and its inputs become ONLINE. Its settings and switches are written twice more with different values and read back each time, and a volt-var or volt-watt function is given a curve. It is disabled again, and its inputs lose the ONLINE flag.
  • Not supported. The enable output refuses a command, and the outstation serves none of the function's points.

The device-profile set has one check, PROFILE-001. It compares what the outstation serves with its DNP3 Device Profile document, given with --device-profile FILE: a point declared and not served, served and not declared, or in class 0 when the document says otherwise fails it.

The deviation set

The deviation set has the master break a protocol rule on purpose and requires what the standard requires of the outstation in return. These checks write nothing to the outstation. They are run only with --allow-deviations, and are reported as not run without it.

py1815-master evaluate --outstation lab=192.0.2.10:20000 --check deviation --allow-deviations

A run with --allow-deviations sends the outstation malformed traffic

The checks send frames with bad checksums and wrong lengths, segments out of place, and withhold confirmations the outstation asked for. An outstation that conforms discards the frames and reports its events again. Use it on a device on a bench.

Check What the master does What it requires
LINK-001 Sends a read in a frame whose header checksum is wrong No answer
LINK-002 Sends a read in a frame whose data checksum is wrong No answer
LINK-003 Sends a read in a frame with its last octet missing No answer
LINK-004 Sends a read in a frame whose length octet claims more than the frame carries No answer
TRANSPORT-001 Sends a read as a segment that is not a first segment No answer, and the next read is answered
TRANSPORT-002 Sends a read whose final segment never comes No answer, and the next read, which begins a new series, is answered
CONFIRM-001 Reads the events and sends no confirmation The same events are reported again
CONFIRM-002 Reads the events and confirms the wrong sequence number The same events are reported again
CONFIRM-003 Reads the events and sends the confirmation after its next request The same events are reported again

The sources:

  • A frame with a bad checksum. IEEE 1815-2012 9.2.4.3 has the checksums checked so that only valid data pass up from the data link layer, and the invalid CRC procedure of section 6.6.2 of the DNP Users Group's IED Certification Procedure requires that such a frame draws no link confirmation and no response.
  • A segment out of place. IEEE 1815-2012 8.2.4, Table 8-1, as Technical Bulletin TB2013-003 restates it: a segment that is not a first segment is discarded while no fragment is being assembled, and a first segment replaces a series under way.
  • Events and confirmations. IEEE 1815-2012 Table 6-1: a confirmation that does not match is discarded and no events are removed, and a request that arrives in place of a confirmation means the confirmation failed. Sections 8.5.2.2.4, 8.5.3.2.4 and 8.5.4.2.4 of the certification procedure read class data without confirming it and require the same events again.

Each link and transport check first sends a well-formed read, which has to be answered, so that the silence that follows is about the damaged request. Afterwards it sends well-formed reads until one is answered. A frame that was cut short can take the start of the next frame with it, so after a link check up to three reads are sent, and the report notes when the first was not the one answered. After a transport check the first read has to be answered.

A read that has to go unanswered is waited for as long as any other: the response timeout, times the read retries plus one. Each of these checks takes that long at least.

The three event checks work on the events the outstation has to report. A master that polls for events has usually just taken them, so a check that finds none reads again every half second for up to the settling time, and is not applicable when none came. After the events are reported again, they are read once more with a confirmation and must not be reported after that. Events that carry no time cannot be told from later events at the same point, so for those the last step is skipped and noted. A master set to send no confirmations cannot run these checks.

A check of this set begins with every deviation of the master off, so that one left on does not damage the well-formed reads the check compares against. It also holds the master until it ends: no automatic task, repeated scan or other caller sends that outstation a request while the check runs, so none is damaged by the check's deviation and none comes between its steps. Whatever deviations were on before the check are on again when it ends, and the same is so for a run that is cancelled part way.

Two events can be equal in every field. An event that was reported twice has to be reported twice again.

What counts as supported

The run begins by reading which points the outstation serves: a class 0 read, a read of output status, and a read by range of every other point of the profile. These reads are made with every deviation of the master off. A point is supported when one of those reads returned it. A check reads only served points, and is not applicable when the points it is about are not served.

What a refusal has to be

Where a command is to be refused, the check requires that it is not accepted and that nothing changed. The status it is refused with is the outstation's to choose: one other than the usual status is reported as a note.

Waiting

A device takes time to stop, to close a switch, or to report a new setting. Where a check waits for one of these it reads again every half second for up to the settling time, 5 seconds unless --settle says otherwise, and fails with the last thing it read.

Curves

The number of curves an outstation stores is its own. The run finds it by selecting each curve in turn until one is refused, up to 64. --curves N states it instead, and then CURVE-001.2 checks that curve N + 1 is refused.

Sample curves are written for the volt-var and volt-watt functions. A function that follows another kind of curve has its other settings checked, and its curve setting is left unwritten and noted.

What a run leaves behind

A check puts back what one command restores, as it found it: the connect switch, the two permissions, and whether the DER is started. Settings and curves stay as the check last wrote them. Every function a check enabled is disabled when the check ends, including a function that was enabled when the run began, which the report notes. No function names a curve afterwards.

When something cannot be put back, the report says so in a note on that check.

The report and the traffic

--report FILE also writes the report as JSON:

{
  "tool": "py1815-master evaluate",
  "version": "0.3.0",
  "outstation": "lab at 192.0.2.10:20000, outstation 1024",
  "started": "2026-10-09T16:39:39+00:00",
  "allow_control": true,
  "allow_deviations": false,
  "tables": "IEEE Std 1815.2-2025",
  "summary": {"passed": 34, "failed": 0, "not_applicable": 1, "not_run": 0},
  "results": [
    {
      "id": "SERV-001",
      "title": "Cease to energize and return to service",
      "verdict": "passed",
      "detail": "",
      "notes": ["the stop was seen under way", "the start was seen under way"],
      "requests": 90,
      "seconds": 1.61,
      "frames": [318, 551],
      "packets": [321, 554]
    }
  ]
}

--capture FILE writes every frame of the run to a pcap file, as it does for the console. packets is the first and last packet of a check in that file, by the number Wireshark shows for each. It is null when no capture is written. The printed report gives the same range for a check that failed, so the exchange that failed it can be found.

frames counts DNP3 frames from 1 in the order they crossed the wire, as the master's trace does. A capture also holds each connection's TCP handshake, so a frame's number is not its packet's.

Settings

Every setting is also in the configuration file, under evaluate, and the outstation's address, link addresses, TLS files and timeouts come from the file or the same flags the console takes.

py1815-master evaluate lab --config master.json --allow-control \
    --check der --report lab.json --capture lab.pcap
Flag Setting Meaning
NAME The outstation to evaluate, when the configuration has more than one
--list Print the checks and exit. Nothing is sent
--check NAME evaluate.checks Run only this check or set. May be repeated, and replaces the list in the file. All of them when not given
--settle SECONDS evaluate.settle How long to wait for the outstation to reach a state it was commanded to. 5 when not given
--curves N evaluate.curves How many curves the outstation stores. Found by selecting each when not given
--report FILE evaluate.report Also write the report as JSON
--allow-control allow_control Run the checks that write
--allow-deviations evaluate.allow_deviations Run the checks that have the master break a protocol rule
--device-profile FILE defaults.device_profile The Device Profile document PROFILE-001 compares with
--capture FILE capture Write the traffic to a pcap file

From Python

import asyncio

from py1815.master import Outstation
from py1815.master.evaluate import evaluate
from py1815.profile import load


async def main() -> None:
    outstation = Outstation("lab", host="192.0.2.10")
    await outstation.connect()
    await outstation.idle()
    try:
        report = await evaluate(outstation, load.load(), commanding=True, deviating=True)
    finally:
        await outstation.close()
    for line in report.lines():
        print(line)


asyncio.run(main())

report.results holds a Result for each check, with its verdict, and report.failed says whether any failed. evaluate_loopback runs the same checks against a session in the same process, with no socket and no waiting, which is how this library's own tests run them.

Writing a check

A check is a function that takes a Bench and yields requests. Bench has the requests a check is made of, each called with yield from: obtain, online, offline, state and value read a point; set and latch write one and return the status; eventually repeats a read for the settling time. A check fails by raising Failed, or through bench.require.

from py1815.master.bench import Bench, Check, NotApplicable
from py1815.master.checks import CATALOG
from py1815.master.evaluate import evaluate
from py1815.profile.model import Kind


def started_is_reported(bench: Bench):
    if not bench.supported(Kind.BI, 14):
        raise NotApplicable("the outstation does not serve BI14")
    started = yield from bench.state(bench.map.point(Kind.BI, 14))
    bench.require(started, "the DER is not started")


mine = Check("SITE-001", "The DER is started", False, started_is_reported)
report = await evaluate(outstation, point_map, checks=[*CATALOG, mine])

The third argument says whether the check writes. One that does is run only when commanding is set.

A check that has the master break a protocol rule is made with deviates=True, and is run only when deviating is set. bench.deviate("corrupt_header_crc") turns a deviation on until the check ends, bench.conform() turns it off sooner, bench.unanswered(what) sends a small read that has to draw no answer, and bench.answers(after) sends reads until one is answered. not_answered and events_kept in py1815.master.checks build the checks of the deviation set from these.